The DGR is the daily record of how a solar plant performed. Here is what goes in it, how the key figures are calculated, and why most plants should stop building it by hand.
A daily generation report (DGR) summarises a solar plant’s performance for one day: how much energy it generated and exported, how much sunlight it received, how efficiently it converted that sunlight, and what stopped it generating. Asset owners, O&M teams, lenders and offtakers use it to track the plant day by day.
PR = energy generated ÷ (installed DC capacity × POA irradiation ÷ 1 kW/m²). A plant of 1,000 kWp that received 5.5 kWh/m² and generated 4,400 kWh has a PR of 4,400 ÷ (1,000 × 5.5) = 80%.
CUF = energy generated ÷ (capacity × 24 hours). The same plant, measured against 1,000 kW over one day, has a CUF of 4,400 ÷ 24,000 ≈ 18.3%. Contracts differ on whether AC or DC capacity is used, so the definition should be stated on the report.
Specific yield = energy generated ÷ installed DC capacity: 4,400 ÷ 1,000 = 4.4 kWh/kWp for the day.
An automated DGR reads directly from the plant’s database, applies the agreed formulas, checks the data for gaps and impossible values, and produces the PDF and Excel versions on schedule. Automated reporting at Mishra Technologies.
Questions
A daily generation report: the daily summary of a solar plant's energy generation, irradiation, performance ratio, CUF, availability and downtime.
Energy generated divided by installed DC capacity multiplied by plane-of-array irradiation divided by 1 kW/m².
Capacity utilisation factor: energy generated divided by plant capacity multiplied by the hours in the period. Contracts specify whether AC or DC capacity is used.
Yes. It can be generated directly from the plant database with built-in checks, and delivered as PDF and Excel on schedule.